ESS tip at start-up system with Pylontech batteries
Lithium batteries are transported at 50% load in accordance with ADR rules. When X number of pylontech modules are connected this may lead to a minor imbalance.
To avoid this carry out the following steps with every new installation:
- Select Remote Console via the VRM portal
- Under device list select ‘Settings’
- Select ‘ESS’
- Select ‘Mode’
- Select ‘Keep batteries charged’
- After 24 hrs select ‘Optimised (without battery life)’: the system now returns to ESS mode
Show 2 photos