GHG2650010R0001

Explosionproof safety switches are used to cut power to electrical installations during maintenance or other work. Safety switches (EMERGENCY STOP function) are characterised by their yellow/red padlock bracket and a forced opening of the main contacts (according to EN60024-1); standard safety switches have a black padlock bracket. The switches can be locked with 3 padlocks. The enclosures are made of glass-fibre reinforced polyester and so are suited for applications in aggressive and heavy-duty conditions.

GHG2650010R0001
Show photo

Product specifications

Order refer. GHG2650010R0001
Material glass-fibre reinforced polyester
Terminal 1 x 50/70 mm²
No. of poles 3+1NO/NC
Nominal current 125
Entries 2xM63 + 1xM25
Weight 16,00 kg
Ambiant temperature -55°C - +45°C
Ex Certificate BVS22ATEXE018X

Classification

  • II 2 G Ex db eb IIC T6 Gb
  • II 2 G Ex db eb ia II C T6 Gb
  • II 2 D Ex tb IIIC T80°C Db

Zone

0 1 2
20 21 22

General technical specifications

Protection IP66
Guideline ATEX
Manufacturer Cooper - Eaton
Suited for
Zone 1 Zone 2
Zone 21 Zone 22

Dimensional sketches

Product code Dimensions
A B C D E F G H I
GHG2650010R0001 271 247 544 520 275 7 11 12 211